Phase 1 - Investigation - Migrating PLC

· 4 min read
Adrian Littlejohns
Industrial Process Control and Automation Enthusiast

Today's Tasks

  1. Begin creation of SCL functions which didn't migrate.
    1. Is _STD_DB_BUFFER [DB190] actually employed?
    2. Create replacement for "SBL Reset Tmp Logg Data"
    3. Investigate Danfoss VLT [FC2007]

Is _STD_DB_BUFFER [DB190] actually employed?

Method

  1. Investigated the sql TPM database for table names which included the word "log" and viewed the top 1000 rows from each.
  2. Investigated the TPOperatorDB for table with log in their name and queried, ordering by date in descending order to get the most recent entries.
  3. WW tags of interest in investigation of WW SCADA app.
  • MemM_OPLoggerItem
  • STD_MemM_OperLogging
  • STD_MemM_ForceLog
  • STD_MemM_ForceLogging
  • STD_MemM_ParLog
  • STD_MemM_ParLogging
  • MemM_OPLoggerItem
  • STD_MemM_LogStepDesc

Results

  1. TPM
  • There were no data records in the observed database tables.
  1. TPOperatorDB
  • There are recent entries in this table, warranting further investigation into the data source.

Conclusion

  • The SCADA system is not storing data from "_STD_DB_BUFFER"
  • PLC - Cannot find evidence of DB190 access from SCADA/HMI. However, the contents of DB190 maybe mapped to another location, via methods which don't show in a Cross-Ref. Considering time required for further investigation , decided to not define a new UDT190 to enable slice operations, but instead to employ a non-optimised block interface and employ the AT instruction to enable access to W0 of the String variables, [String0 , String1]

Create replacement for "SBL Reset Tmp Logg Data"

created "SblResetTmpLoggData"

FUNCTION "SblResetTmpLoggData" : Void
{ S7_Optimized_Access := 'FALSE' }
VERSION : 0.1
VAR_OUTPUT
LoggData : "_STD_LOG_Data";
END_VAR

VAR_TEMP
string0 : String[30];
string0Word AT string0 : Array[0..15] of Word;
string1 : String[20];
string1Word AT string1 : Array[0..10] of Word;
END_VAR


BEGIN
#LoggData.I1 := l#0;
#LoggData.I2 := l#0;
#LoggData.I4 := l#0;
#LoggData.I5 := l#0;
#LoggData.I6 := l#0;
#LoggData.I7 := l#0;
#LoggData.I8 := l#0;
#LoggData.I9 := l#0;
#LoggData.I10 := l#0;
#LoggData.I11 := l#0;
#LoggData.I12 := l#0;
#LoggData.I13 := l#0;
#LoggData.I14 := l#0;
#LoggData.I15 := l#0;
#LoggData.I16 := l#0;
#LoggData.I17 := l#0;
#LoggData.I18 := l#0;
#LoggData.I19 := l#0;

#LoggData.Real0 := 0.0;
#LoggData.Real1 := 0.0;
#LoggData.Real2 := 0.0;
#LoggData.Real3 := 0.0;
#LoggData.Real4 := 0.0;

#string0Word[0] := W#16#1E00;
#string1Word[0] := W#16#1400;

#LoggData.String0 := #string0;
#LoggData.String1 := #string1;




END_FUNCTION

See Replace usage of SBL Reset Tmp Logg Data for details.

Investigate Danfoss VLT

Viewing the classic program on-line revealed that the all drives had a comms fault and the comms fault was not used.

See :- Investigate Danfoss VLT

Compile Error: _STD_LogCopyToBuffer

F1 help

Help on message 604:4549 
Description

The error occurred because you are using an instruction that accesses the DB or
DI register. However, you did not load a DB to the register beforehand.

Examples of instructions that access the DB/DI register are:

L DBNO

The instruction loads the number of a global data block opened via the data
block register into accumulator 1.

L DINO

The instruction loads the number of an instance data block opened via the data
block register into accumulator 1.

Partially qualified addressing

The addressing of DB tags without specification of the DB name or DB number is
referred to as partially qualified addressing (for example, L %DBW0).
The program accesses the data block that is currently in the DB or DI
register.

Resolution

You have the following options to remedy the error:

Enter a fully qualified address. Fully qualified addresses include the
specification of a data block (e.g. L %DB1.DBW0 or L "Motor".Value).

Load a DB to the DB register with the instruction OPN or OPN DI.

Note

Parameter passing via registers

On S7-1500 CPUs, the values from the registers, accumulators and the status
word are generally never transferred to called blocks. The instructions "CC"
and "UC" are the only exceptions. If you use "UC" or "CC" and want to pass the
parameters to the called block by using registers, the status word or
accumulators, you have to select the "Parameter passing via registers" option
in the properties of the called block. Note that this option is only available
for STL blocks with standard access and the block can have no formal
parameters.



For additional information, refer to "See also".


--------------------------------------------------------------------------------

See also

Migration of STL programs to S7-1500 (S7-1500)


References